EX9015H-M - Modbus 6 RTD input module, individual channel conf.
EX9015H-M 16 bit RS485 remote I/O Modbus RTU module for RTD. 6 differential analog In. Individual channel configuration
Omschrijving
The EX9015H-M Analog In 16 bit Modbus RTU module for resistance temperature (RTD) detectors excels at use for temperature measurement with a resistance temperature detector. The Analog In 16 bit module has 6 individually configurable differential isolated channels and 2/3-wire RTD (Pt, Ni, Cu) Sensor. The Analog In 16 bit module supports parity types None/Even/Odd, has a 12 samples/sec. sampling rate and a built-in open-loop detection. The Analog In RS485 module can be used in a wide temperature range
Features:
- 6 digital In (16 bit)
- Sample rate 12 Hz
- Sensor Type PT100, PT1000, CU100, CU1000, NI120
- Sensor input 2/3-wire RTD (Pt, Ni, Cu)
- Modbus-RTU
- Individual channel configuration
Kenmerken
Interface |
|
---|---|
Communicatie | RS485 |
Snelheid | 1200 - 115200 bps |
Connector | Terminal Block |
Protocol | Modbus RTU |
Input/output |
|
Type | RTD |
Kanalen in | 6 |
Isolatie | Yes |
Analoog-in |
|
Kanalen | 6 differential |
Resolutie | 16 bit |
Totale steekproef snelheid | 12 Hz |
Nauwkeurigheid | ± 0.05 % |
Zero drift | ± 0.5 µV/°C |
Span drift | ± 20 ppm/°C |
Type sensor | PT100, PT1000, CU100, CU1000, NI120 |
Sensor ingang | 6 x 2/3 wire |
Kenmerken |
|
Isolatiespanning | 3000 V |
Extra’s | Individual channel configuration, 3.5 character between command, 50/60hz rejection |
Systeem |
|
Vermogen max. | 1 W |
Stroomtoevoer | 10~30V DC |
Behuizing |
|
Doorgaan | Din Rail Mounting |
Afmeting | 100 x 70 x 25mm |
Gewicht | 110g |
Omgeving |
|
Bedrijfstemperatuur | -25~75°C |
Opslag temperatuur | -30~75°C |
Certificarie | CE / FCC / WEEE / RoHS |
Andere |
|
inbegrepen bij levering | Din Rail Mounting Kit |